HP's Cookie Cutter Data Center: Flexible DC

HP sees a future in flexible, modular data center designs. FlexDC from HP's Critical Facilities Services division is a modular data center design that covers all the physical requirements including building, cooling and electrical power. Similar to the design build methodology used in retail and warehouse building where a company contracts for a fixed amount of square footage at a location and takes the keys when it is complete, HP Flex Data Center is built from predefined components, shipped to

July 27, 2010

4 Min Read
Network Computing logo

HP sees a future in flexible, modular data center designs. FlexDC from HP's Critical Facilities Services division is a modular data center design that covers all the physical requirements including building, cooling and electrical power. Similar to the design build methodology used in retail and warehouse building where a company contracts for a fixed amount of square footage at a location and takes the keys when it is complete, HP Flex Data Center is built from predefined components, shipped to site, and put together. HP claims to cut capital costs by as much as 50 percent and time to build in under a year.

Kenneth Miller from the Midwest ISO, and an InformationWeek Analytics contributor, said  "The contained data centers that Microsoft championed addressed the compute portion of data center modularity but not the physical facility itself. Data centers [delivered in modular components] like Flex DC are more complicated on the design side due to local resources, building codes, support legacy equipment and specific customer requirements, but as long as the incremental building blocks are sized right, can remain standardized and meet an organization's technical requirements, this approach will meet many organization's needs."

HP's butterfly design contains a central building that contains the administrative offices, loading dock and space for storage and offices. The work is done in the quadrants which can be built in 400 or 800 KW units complete with heating and cooling. You supply the racks and computer equipment. The entire building is approximately 25,000 square feet with each quadrant between five to six thousand square feet each. HP is targeting  power usage efficiency (PUE) rating which is calculated as a ratio of power for facilities divided by a the power used for computing (lower is better) of 1.25.

You can start with a core and one quadrant and add more quadrants as needed. Of course you achieve better cost savings per megawatt by building it all at once. The 50 percent cost savings cited by HP is based on a 3.2 MW butterfly. HP achieves the cost savings by leveraging its supply chain. By standardizing on the design and component selection, they reduce the number of parts and the labor to build each data center to spec. HP achieves economies of scale that they pass along to the customer. If you want custom features, that will, of course, change the price and the time to build.

Built on a slab, the heating and cooling is run over head through raised plenums. Cold air is vented to the cold aisle while hot air is extracted from the hot aisle. HP has four cooling designs: direct evaporative with direct expansion, indirect evaporative with direct expansion, Kyoto cooling, and air-to-air heat exchange with direct expansion. The cooling units are selected based on the local environmental conditions. To maximize floor space, the HVAC units are located outside the building with the plenums running through the outer wall. That keeps water, if evaporative systems are used, outside of the data center and away from electrical equipment.  The electrical systems are designed to be efficient and where possible, HP took costly transformers and converters out of the design. The redundant design includes multiple generators, UPSs and power distribution units in keeping with reliability best practices. Any system can go down and power will remain uninterrupted. While Flex DC isn't certified using the Uptime Institutes tier system, HP designed it to be fault tolerant and reliable. Each quadrant is autonomous and run separately from the other quadrants.

While Flexible DC is not a turnkey data center---you still have to supply the computing resources--it is designed to fit most situations, and since you can start with a relatively small build, 400KW in one quadrant, you can expand as you grow. This follows a trend in computing with the likes of Cisco, Dell, and  HP, along with their partners, producing fixed, stamp-sized computing platforms complete with servers, storage and networking. They can quickly deliver pre-built systems that will fit most general computing needs cheaper than custom designs.  

If you are looking at replacing an existing data center or modernizing an existing data center, HP's Flexible DC is worth a look. If HP can make good on their claim of reduced capital costs plus the operational cost savings in reduced facilities power, combined with operation savings that can be found in modern computing, storage and networking gear—less power draw, less heat generation meaning less cooling required—they are presenting a compelling business case.

SUBSCRIBE TO OUR NEWSLETTER
Stay informed! Sign up to get expert advice and insight delivered direct to your inbox

You May Also Like


More Insights